IEC-101 Slave ProLinx Communication Gateway 101S Protocol Configuration
IEC 60870-5-101 v3 Slave (Firmware version 3.xx) Protocol Manual
ProSoft Technology, Inc. Page 35 of 159
August 6, 2010
2.1.26 Time Type
[0] = None, [1] = CP24, or [2] = CP56
Separate parameters exist for multiple point types. This parameter defines the
time format used with data events.
2.1.27 Use Balanced Mode
Y - YES or N - NO
This parameter specifies if the port will use balanced mode. If balanced mode is
used, only one controlled station will be permitted on the port. If unbalanced
mode is used, multiple controlled stations can be used on a port.
Refer to gateway Initialization for more information on these modes.
2.1.28 Retry Count
0 to 255
In balanced mode, this parameter specifies the number of retries (0 to 255) if a
response is not received. In unbalanced mode, this parameter is ignored.