5.6.5 Additional Advantages to Substation Configuration
Description Language (SCL)
ICD files list the functionality (via Logical Nodes) and data objects (Data
Attributes) available for the IED
The device’s ICD files list the communication service capabilities of the IED,
e.g. is File Transfer supported
The ICD tells what’s in the DATA-SETs.
It lists the Report Control Blocks, and if the DATA-SET for it can by
dynamically assigned.
When gathering data from the IED for archiving purposes, the database is
simply built because of the descriptive names coming from the devices.