MVI69-PDPMV1 CompactLogix or MicroLogix Platform Ladder Logic
PROFIBUS DPV1 Master User Manual
ProSoft Technology, Inc. Page 23 of 225
July 8, 2011
4 The following illustration shows an example where the module was
configured for a block transfer size of 60 words (input block size = 62 words,
output block size = 61 words):
Enter the Input Block Size and Output Block Size parameters according to
the Block Transfer Size to use:
Block Transfer Size Input Block Size Output Block Size
60 62 61
120 122 121
240 242 241
Important: You must set the Block Transfer Size in ProSoft Configuration Builder to match the
block size for the Add-On Instruction, otherwise the module may not function correctly.
5 On the C
ONNECTION tab, check or un-check, as desired the Major fault option.