Diagnostics and Troubleshooting MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform
User Manual PROFIBUS DPV1 Master
Page 144 of 225 ProSoft Technology, Inc.
July 8, 2011
5.3 LED Indicators: Front of MVI69 Module
The LEDs indicate the module’s operating status. The module has two sets of
LED Indicators:
MVI69 Module Status LEDs on the front of
the module near the top
PROFIBUS Master Status LEDs behind the
door on the front of the module.
5.3.1 Module Status Indicators
Indicator Color Status Indication
CFG Green ON Configuration/Debug Port is active
OFF Configuration/Debug Port is inactive
P1 Not Used
P2 Not Used
APP STATUS Amber ON
Configuration Error: This LED is illuminated
when the PROFIBUS and module CRC values
do not match between input/output blocks.
Verify that the values match the values
generated with the Calculate Checksums button
in ProSoft Configuration Builder. If they do not
match, you must manually change the values at
the appropriate address locations listed in the
Input and Output block definitions in this manual.
OFF Normal operation
BP ACT Amber ON
The LED is ON when the module is able to
communicate over the backplane.
OFF
The LED is OFF when the module is unable to
communicate with the processor. The processor
is either absent or not running.
BATT Red OFF The battery voltage is OK and running.
ON
The battery voltage is low or the battery is not
present. The battery LED will illuminate briefly
upon the first installation of the module or if the
unit has not had power for an extended period.
This behavior is normaL; however, should the
LED come on in a working installation, please
contact ProSoft Technology.