COMMAND 35 - Write Range Values
Description
This command writes the Upper and Lower range of the Primary Variable
Write Parameters
Word High Byte Low Byte
0 Range Units Code Floating Point Upper Range Value (Byte 0)
1 Floating Point Upper Range Value (Byte 1) Floating Point Upper Range Value (Byte 2)
2 Floating Point Upper Range Value (Byte 3) Floating Point Lower Range Value (Byte 0)
3 Floating Point Lower Range Value (Byte 1) Floating Point Lower Range Value (Byte 2)
4 Floating Point Lower Range Value (Byte 3) Floating Point Lower Range Value (Byte 3)
Floating Point Data Returned
Word High Byte Low Byte
0
1
Upper Range Value
2
3
Lower Range Value
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Range Units Code 0