Reference PTQ-104S Rev2 Quantum Platform
User Manual IEC 60870-5-104 Server for Quantum
Page 162 of 195 ProSoft Technology, Inc.
February 22, 2013
If this parameter is set to 0, the module will not generate events for any points. A
non-zero value will configure how frequently the module will scan for events in
the database.
Data Type Level
The user may configure if a data type should generate events or not. Each data
type has a configuration parameter to control the generation of events:
In the example above, only the M_SP_NA points would generate events.
Point Level
You can configure whether or not each point should generate events on a point-
by-point basis by using the Group field for each point configuration. Set the value
as 40000000 to disable the generation of events for any specific point.