ILX69-PBM ♦ CompactLogix or MicroLogix Platform Contents
PROFIBUS Master Communication Module User Manual
ProSoft Technology, Inc. Page 19 of 124
February 4, 2015
If the ILX69-PBM is linked with only one other device on the bus, both devices must be
connected to the ends of the bus line. These devices must deliver the supply voltage for the
termination resistors. If three or more devices are connected to the bus, the ILX69-PBM can
be connected at any desired position.
Up to 32 PROFIBUS devices can be connected to one bus segment, without repeaters. If
several bus segments are linked to each other with repeaters, there can be up to 127
devices on the network.
The maximum permissible cable length of a PROFIBUS segment depends on the baud rate
used, see the following table.
Only PROFIBUS certified cables, preferably the cable type A, should be used. The following
table contains important electrical data concerning PROFIBUS certified cable:
35 to 165 Ohm at frequencies from
3 to 20 Mhz
Capacity per units
length