MVI69-MCM ♦ CompactLogix or MicroLogix Platform Configuring the MVI69-MCM Module
Modbus Communication Module User Manual
ProSoft Technology, Inc. Page 27 of 167
March 22, 2011
10 The imported rung will contain the Add-On instruction with two CPS
instructions as follows below. The CPS instructions are set by default for a
length of 62/61 words as follows:
Edit the above CPS instructions Length field values according to the following
table.
"Block Transfer Size Parameter" –
60/120/240 options)
Ladder Routine window:
Connection Parameters: CPS instructions Length field values:
Input Size: Output Size:
62 61 62 61
122 121 122 121
242 241 242 241
2.1.4 Set the Read/Write Data Lengths
1 The imported rung contains the MCMDATA
object Tag arrays R
EAD
D
ATA
and
W
RITE
D
ATA
set to the factory default values of 480. These tags will contain:
o
R
EAD
D
ATA
- data area copied from the module to the processor
o
W
RITE
D
ATA
- data area copied from the processor to the module