Contents MVI56E-DNPNET ♦ ControlLogix Platform
User Manual DNPNET Ethernet Client/Server Communication Module
Page 16 of 140 ProSoft Technology, Inc.
February 13, 2015
Enter the slot number in the rack where the MVI56E-DNPNET
module is located
CONFIGURATION ASSEMBLY INSTANCE
Important: You must select the COMM FORMAT as DATA - INT in the dialog box, otherwise the module will not
communicate over the backplane of the ControlLogix rack.
4 Click OK to continue.
5 Edit the Module Properties.
Select the REQUESTED PACKET INTERVAl value for scanning the I/O on the module. This
value represents the minimum frequency at which the module will handle scheduled
events. This value should not be set to less than 1 millisecond. The default value is 5
milliseconds. Values between 1 and 10 milliseconds should work with most applications.