Reference 5204SE-MNET-PDPMV1 ProLinx Gateway
User Manual Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master
ProSoft Technology, Inc. Page 211 of 235
December 22, 2009
New Slave Address
Range 0 to 125
Specifies the new address of the slave.
Slave Ident Number
Ident number for the slave, which address should be altered.
No_Add_Change
This parameter specifies whether it is allowed to change the slave address again
at a later stage. If this is not allowed, then it is only possible to change the
address with this function after initial reset. After the initial reset, the slave takes
the default address 126.
00h Change of address is still possible at a later stage
01h - FFh Change of address is only possible after the initial address (the
default address = 126)
Error Code [1 ... 4]
If 'Return Code' equals 8030h ('Negative indication from lower layer'), status
values according to the DP-specification is available in 'Error Code 1'. Error
Codes 2 to 4 are reserved.
(See Return Codes (page 219) and Error Codes)
Fault Information and Extended Fault Information
"Fault Information" Contents "Extended Fault Information" Contents
0001h Current Slave Address out of range -
0002h New Slave Address out of range -
000Ah Failed to send Global Control
request
For additional fault information, see Return
Codes (page 219)
000Bh Remote Station Failure For additional fault information, see Return
Codes (page 219)
00FFh Module offline (not initialized or no valid database)
Slave Data
With this parameter it is possible to deliver user specific data. The data is stored
in the slave if possible (EEPROM, FLASH, etc.)