ProSoft Technology ProLinx-HART Specifikace Strana 79

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 104
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 78
ProLinx-HART ♦ ProLinx Gateway Reference
HART Master with Analog I/O Driver Manual
ProSoft Technology, Inc. Page 79 of 104
October 13, 2011
COMMAND 57 - Read Unit Tag Descriptor Date
Description
This command reads an ASCII Tag which identifies the device, an ASCII descriptor of the
device and the last Date it has been configured.
Write Parameters
NONE
Floating Point Data Returned
NONE
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 TAG ASCII Character 0 TAG ASCII Character 1
2 TAG ASCII Character 2 TAG ASCII Character 3
3 TAG ASCII Character 4 TAG ASCII Character 5
4 TAG ASCII Character 6 TAG ASCII Character 7
5 Descriptor ASCII Character 0 Message ASCII Character 1
.
.
.
.
.
.
12 Descriptor ASCII Character 14 Message ASCII Character 15
13 Date Date
14 Date 0
Zobrazit stránku 78
1 2 ... 74 75 76 77 78 79 80 81 82 83 84 ... 103 104

Komentáře k této Příručce

Žádné komentáře